ECL100 Eddy-Current Displacement Sensor

  • High Performance
  • 0-10V and 0-20mA Linear Outputs
  • Adjustable Zero (Local and Remote)
  • 12-24VDC Power
  • Visual Range Indicator
  • DIN Rail Mount
  • Multi-Channel Sync Capabilities
  • Easy Access Terminal Blocks




Specifications

Typical specifications for standard targets and probes. Actual values depend on probe, target, and calibration.

Resolution:
RMS at mid-range for most calibrations. See Ranges below for resolution details.
DC-1kHz - 0.004% of Range RMS
DC-10kHz - 0.008% of Range. RMS
DC-80kHz - 0.06% of Range RMS
Nonlinearity Nonferrous: ±0.25% of Range.
Ferrous: ±0.50% of Range.
Temperature Drift of Probe at mid-range ±0.02% of Range/°F
±0.04% of Range/°C
Outputs

0-10VDC
0-20mA

Input Power 12-24VDC
130mA at 15VDC
Operating Temperature 40°F-120°F
4°C-50°C
Probe Operating Temperatures

Standard Probes:
-10°F-+250°F
-25°C-+125°C

High Temperature Probes:
-10°F-+400°F
-25°C-+200°C

 

Ranges

calA specific range and resolution will require a particular probe size/model. Range/Resolution may also be affected by the target material.

Probes are identified by their internal coil diameter.
A U5 probe has a 5mm coil, U8 a 8 mm coil etc. Larger ranges require larger coils/probes.

Custom ranges are always available.

Listed specifications are for standard target materials.

Range Chart

Range
mm
inch
Near Gap
mm
inch
Probe Target
Typel
Resolution (RMS)
µm
µinch
1kHz 10kHz 80kHz
0.50
0.020
0.05
0.002
U3 Nonferrous 0.02
0.8
0.04
1.6
0.30
13
Ferrous 0.04
1.6
0.08
3.2
0.60
25
1.25
0.050
0.25
0.010
U5 Nonferrous 0.05
2.0
0.10
4.0
0.75
30
Ferrous 0.10
4.0
0.20
8.0
1.5
60
2.00
0.080
0.35
0.015
U8 All 0.08
3.2
0.16
6.4
1.2
48
3.50
0.140
0.60
0.025
U12 All 0.14
5.6
0.28
11
2.1
84
5.00
0.200
0.75
0.030
U18 All 0.20
8.0
0.40
16
3.0
120
8.00
0.320
1.25
0.050
U25 All 0.32
13
0.64
26
4.8
190
12.5
0.500
1.50
0.060
U38 All 0.5
20
1.0
40
7.5
300
15.0
0.600
2.00
0.080
U50 All 0.60
24
1.2
48
9.0
300

 

Mechanical